Detail Spec. of LPCB Our fire resistance cable were get the British BRE company"s LPCB authentication.BS7629BS 6387EN 50200BS 5839-1Standard 60C W ZPH120Standard BS7629-1:2008 British Standard Specification for 300/500V fire resistant cable have low emissions of smoke and corrosive gases when a......
| BS7629 | BS 6387 | EN 50200 | BS 5839-1 |
| Standard 60 | C W Z | PH120 | Standard |
BS7629-1:2008 British Standard Specification for 300/500V fire resistant cable have low emissions
of smoke and corrosive gases when affected by fire.
BS 6387:1994 Performance requirements for cable required to maintain circuit integrity under fire
conditions.
C-Resistance to fire at 950 oC for 180 minutes
W-Resistance to fire at water at 650oC for 30 minutes
Z-Resistance to fire and mechanical shock to 950oC for 15 minutes
EN 50200: 2006 Method of test for resistance to fire of unprotected small cables for use in emergency circults.
European Committeee for Electrotechnical Standardizations, Brussels, 2006
Authentication No.: 1383a/1383b
Formation: 2cores, 3cores or 4cores
Section: 1.0mm sq, 1.5mm sq, 2.5mmsq, 4.0mmsq
Conductor: Top quality bare copper
Insulation: Top quality Silicon Rubber En12
Jacket: Special Low smoke zero halogen thermoplastic compound
Withstand heat: Special mica tape
Shield: Top quality glass fiber tape or AL for(Optiona)
Drain draw: Tinned copper
Vated voltage:300/500V
Packaging Details: 100 Meter/Rool, 200 Meter/Wooden drum, 500 Meter/Wooden drum, Carton & Pallet


Stranded Copper Wire Flexible Wire Thhn Wire
Copper Core PVC Insulated Tw Thw 12 Electrical Wire
UL1015 Tinned Copper PVC Insulated UL Listed Cable Wire
Arc-Welding Cable, Welding Machine Cable, Flexible Cu/Epr, 600 V (ICEA S-75-381/NEMA WC 58/CAN/CSA C22.2 No. 96/UL 1581 )
UL 1581 PVC Wire Cable Tinned Copper Conductor Electrical Cable for Internal Wiring
UL 1581 PVC Wires Tinned Copper Conductor for Internal Wiring